Product Description

Electronic Alternator Voltage Regulator is product of M/s Hipo Power System. AGR - 1 is full wave phase controlled thyristor type AVR & forms part of excitation system for brush-less/slip ring type generator. Use of high efficient & sensitive semiconductors, positive voltage build-up is ensured from lower residual voltage level. AGR -1 derives power from main stator & senses the average value of either two phases or single phase. AGR-1 provides under-speed excitation protection, by reducing the output voltage proportionally with speed below a preset threshold.

TECHNICAL SPECIFICATION:

SUPPLY/SENSING VOLTAGE.

(Link ‘V’ & ‘N’ for single phase operation)

225 – 475 VAC 2 phase & Neutral at U, V & N.

130 – 275 V ac 1 phase & Neutral at U & N resp.

FREQUENCY. 50 Hz.

OUTPUT.

Voltage.

Current.

Resistance

200 V dc @ 415 / 240 V ac input at F+ & F-.

6.0 A, continuous / 7.5 A transient for 10 secs.

15 ohms min.

REGULATION. +/- 1.0%.

AVR RESPONSE. 20 ms.

UNDER Frq. PROTECTION. @ 47 Hz preset and sealed, Slop – 150% volts/Hz.

BULD UP VOLTAGE. 5 Volts @ AVR terminals.

OPERATING TEMPERATURE. -40 to + 70C.

PROTECTION FUSE. 6.0 A, quick acting (19mm X 5mm glass cartridge)

CONTROLS :

V – Set. To adjust generator output voltage. Clockwise rotation, increases output voltage.

Stab. To prevent voltage hunting. Clockwise rotation, increases damping effect.

U/F Set. To set under frequency knee point. Clockwise rotation, increases knee point setting.

PHYSICAL DIMENTION/WEIGHT :

L x W x H 169mm X 106mm X 45mm

Weight. 425 gms.

MOUNTING. 6.6mm X 2 holes, at center distance of 153.0mm.

IMPORTANT :

· The discrete power component TYN 1225/612 and diode 6A10 can be replaced if failed.

· CHANGE THE SWITCH & DO SHORT (LINK) ‘V’ & ‘N’ FOR 1- PHASE OPERATION.

CAUTION :

Ø Isolate AVR while flashing or insulation testing of the Alternator.

Ø Installation and adjustment must be carried-out by skilled technician only.