Product Description :
This system is forced circulation fully automatic thermic fluid heater where thermic fluid is circulated in a closed loop through heater and user equipment circuit where the heat is dissipated to process. The same thermic fluid is re-circulated through heater for heating. The thermic fluid heater gives high temperature upto 300 oC using thermic fluid oil at near atmospheric pressure as compared to steam heating which requires 85 Kg/Cm2 pressure.

 

Parameter

Unit

Model

ABTH-400

ABTH-600

ABTH-1000

ABTH-1500

ABTH-2000

Heat Output

Kcal/Hr

4,00,000

6,00,000

10,00,000

15,00,000

20,00,000

Max.Fluid Outlet Temperature

oC

300

Max. Head at heater Outlet

M/c

27

Efficiency on GCV

With APH+

%

75

Without APH+

%

70

Rated fuel consumption

Steam Coal

Kg/hr

118

177

296

444

592

Lignite

Kg/hr

152

228

381

571

762

Agro-waste

Kg/hr

162

242

404

606

808

Thermic Fluid Pump Motor

Kw

9.30

11.00

15.00

22.00

30.00

I.D.Fan Motor

Kw

3.70

5.62

11.25

11.25

15.00

Over fire fan motor

Kw

-

1.50

2.25

3.70

3.70

Total Load

Kw

13.00

18.12

28.50

36.95

48.70

Expansion Tank Capacity

Liters

800

800

1000

1000

1250

Overall Dimensions

Length

mm

4600

6000

7500

7800

10000

With

mm

3800

4000

4500

5400

6200

                 

FEATURES

Multifuel Concept

Guaranted output on low grade coal and lignite with GCV upto 3800 Kcal/Kg. Agricultural Wastes such as rice Husk, Bagasse, Groundnut shell, Saw Dust etc.

Highest Efficiency

The combustion chamber dimension and grate area are suitably designed for maximum combustion efficiency on low grade fuel. This system is easily accessible and large heating surface of Thermo Energy Systems heater and air pre-heater assures on unmatched efficiency f 76% (on GCV of coal having 5000 Kcal/Kg.)

Low Power Consumption

Unique design of Thermo Energy Systems heater ensures lowest power consumption over any other competing system available today.

Absolute Safety

External Combustion chamber ensures longer life of heater coil and thermic fluid. No radiation energy is transferred to heater coil in case of power failure ensuring complete safety. Diesel engine driven pump is not required for Fluid tech heater as compared to vertical systems.

 External Furnace

Coal/Lignite is burnt in an external furnace which results in an elimination of any possible hazard to the thermic fluid heater coil. A flue by-pass system is attached for the protection against power failure. The entire furnace is provided with steel casing and the combustion chamber is constructed with best quality high heat duty fire bricks and insulation bricks. Mineral wool insulating panels help minimum heat loss.

Thermic Fluid Heater

Here a nest of concentric helical tube coils is placed within sturdy mild steel shell. The special arrangement of concentric coils ensures optimum heat transfer. The system along with the standard accessories is conveniently mounted on the sturdy steel skid for easy installation.

Safety Controles and Instrumentation

·        Digital Electronic indicator cum controller forward/return temperature for ID fan off.

·        Electronic stack temperature controller shuts of the unit in case of abnormally low temperature.

·        Electronic low level controller in expansion cum deareated tank shuts off the unit in case of low thermi fluid level in tank.

·        Electronic forward high temperature safety controllers shuts off the unit case forward temperature exceeds than minimum recommended temperature.

·        Differential pressure switch shuts of in case of abnormal fluid flow conditions.

·        Pressure gauge for inlet pressure measurement.

·        Pressure gauge for circuit pressure measurement.

·        Audio visual alarm for abnormal operating conditions.

Optional Features

·        Coal cum oil firing system to change over from one fuel to another with minimum down time,

·       Automatic by-pass damper with electromagnetic or pneumatic device.

·        Modulating damper or variable speed drive to control combustion under all operating conditions.